全部 6 个数据中心运行正常

加密货币支付 · 无需身份核验 · 5 分钟以内 内获得 root 权限

轻微 已解决

BMC sensor read errors on L4 nodes in AMS

带外管理——AMS

时间线

  1. 已解决

    Sensor data is complete for every node. Duration: 1 h 4 min. The fixed firmware is being rolled out during regular maintenance; no host reboot is required.

  2. 观察中

    All 9 BMCs have been reset and report cleanly. Watching for recurrence.

  3. 已确定原因

    A BMC firmware version on 9 nodes has a bug in its sensor polling that surfaces after a long uptime. Resetting the BMC clears it without touching the host; we are doing that node by node.

  4. 调查中

    The BMCs on some L4 nodes in AMS are returning sensor read errors since 08:42 UTC. Power and temperature readings in the customer area are missing for those machines. The machines themselves are unaffected.

登录

控制台、账单与带外访问。

还没有账户?

没有单独的注册流程。您的账户会在您 下第一笔订单时自动创建——您在付款步骤中选择邮箱和密码, 机器交付时,控制台也随之开通。

配置服务器

Language