BMC sensor read errors on L4 nodes in AMS
Bant dışı yönetim — AMS
Zaman çizelgesi
-
Çözüldü
Sensor data is complete for every node. Duration: 1 h 4 min. The fixed firmware is being rolled out during regular maintenance; no host reboot is required.
-
İzleniyor
All 9 BMCs have been reset and report cleanly. Watching for recurrence.
-
Neden belirlendi
A BMC firmware version on 9 nodes has a bug in its sensor polling that surfaces after a long uptime. Resetting the BMC clears it without touching the host; we are doing that node by node.
-
İnceleniyor
The BMCs on some L4 nodes in AMS are returning sensor read errors since 08:42 UTC. Power and temperature readings in the customer area are missing for those machines. The machines themselves are unaffected.
Saatler, saat diliminizde () gösterilir.
İlgili sayfalar
- Hizmet durumugpuserver.io'nun her bileşeni ve veri merkezi, beş şehirden 60 saniyede bir yoklanır; 90 günlük kullanılabilirlik ve 2022'den beri olay logu burada yer alır.
- Olay geçmişigpuserver.io'da izlemenin başladığı Eylül 2022'den bu yana yaşanan her olay ve bakım penceresi, ay ay, zaman çizelgesi ve olay sonrası incelemesiyle birlikte.
- Hizmet seviyesi sözleşmesi%99,9 taahhüdü: neyin kesinti sayıldığı, dışarıdan nasıl ölçüldüğü, kaybedilen her dakika için beş dakika süre iadesi ve istisnaların tamamı.
- Ağ25 Gbit/s'e kadar sayaçsız portlar, site başına iki operatör ve bir IX, sürekli DDoS filtreleme, yönlendirilen IPv6 — ve baştan belirtilen, sunmadığımız dört şey.