BMC sensor read errors on L4 nodes in AMS
Gestión fuera de banda — AMS
Cronología
-
Resuelto
Sensor data is complete for every node. Duration: 1 h 4 min. The fixed firmware is being rolled out during regular maintenance; no host reboot is required.
-
En observación
All 9 BMCs have been reset and report cleanly. Watching for recurrence.
-
Causa identificada
A BMC firmware version on 9 nodes has a bug in its sensor polling that surfaces after a long uptime. Resetting the BMC clears it without touching the host; we are doing that node by node.
-
Investigando
The BMCs on some L4 nodes in AMS are returning sensor read errors since 08:42 UTC. Power and temperature readings in the customer area are missing for those machines. The machines themselves are unaffected.
Las horas se muestran en su zona horaria ().
Páginas relacionadas
- Estado del servicioEstado en vivo de gpuserver.io: componentes y centros de datos sondeados cada 60 s desde 5 ciudades, con disponibilidad de 90 días e incidentes desde 2022.
- Historial de incidentesTodos los incidentes y ventanas de mantenimiento de gpuserver.io desde septiembre de 2022, mes a mes, con cronología y revisión posterior al incidente.
- Acuerdo de nivel de servicioEl compromiso del 99,9 %: qué cuenta como inactividad, cómo se mide desde fuera, cinco minutos de plazo por cada minuto perdido, y las exclusiones completas.
- RedPuertos sin contador hasta 25 Gbit/s, dos operadores y un IX por sede, filtrado DDoS permanente, IPv6 enrutado — y las cuatro cosas que no ofrecemos, dichas ya.