BMC sensor read errors on L4 nodes in AMS
Out-of-Band-Management — AMS
Zeitleiste
-
Behoben
Sensor data is complete for every node. Duration: 1 h 4 min. The fixed firmware is being rolled out during regular maintenance; no host reboot is required.
-
Beobachtung
All 9 BMCs have been reset and report cleanly. Watching for recurrence.
-
Ursache erkannt
A BMC firmware version on 9 nodes has a bug in its sensor polling that surfaces after a long uptime. Resetting the BMC clears it without touching the host; we are doing that node by node.
-
Untersuchung läuft
The BMCs on some L4 nodes in AMS are returning sensor read errors since 08:42 UTC. Power and temperature readings in the customer area are missing for those machines. The machines themselves are unaffected.
Zeiten werden in Ihrer Zeitzone angezeigt ().
Verwandte Seiten
- ServicestatusLive-Status jeder gpuserver.io-Komponente und jedes Rechenzentrums, alle 60 Sekunden aus fünf Städten gemessen, mit 90-Tage-Verfügbarkeit und Protokoll seit 2022.
- VorfallshistorieJeder Vorfall und jedes Wartungsfenster auf gpuserver.io seit September 2022, mit Zeitleiste und Nachbesprechung des Vorfalls.
- Vereinbarung zum ServicelevelDie 99,9-%-Zusage: was als Ausfallzeit zählt, wie sie von außen gemessen wird, fünf Minuten Laufzeit zurück je verlorener Minute, und die Ausschlüsse vollständig.
- NetzwerkPorts ohne Volumenbegrenzung bis 25 Gbit/s, zwei Carrier und ein IX pro Standort, ständige DDoS-Filterung, geroutetes IPv6 — und vier Dinge, die wir nicht anbieten.