Core switch line-card failure in REY, row B
Сеть — транзит и пиринг — REY · Внеполосное управление — REY
Хронология
-
Устранено
Every machine in row B has been reachable since 22:22 UTC. Duration of the outage: 54 minutes. The failed card is being replaced under an existing maintenance window; the replacement does not require another interruption. Affected machines receive the SLA extension automatically.
-
Наблюдение
All 14 affected ports are up on the surviving card. We are checking each machine individually before closing this.
-
Причина установлена
A line card in one of the two core switches in REY failed. Row B was dual-homed, but the failover on 14 ports did not complete because the standby links were still training. We are forcing those ports over to the surviving card.
-
Идёт расследование
Machines in row B of REY lost network connectivity at 21:28 UTC. Rows outside B are unaffected. Engineers are on the floor.
Разбор инцидента публикуется здесь в течение пяти дней после устранения.
Время показано в вашем часовом поясе ().