Core switch line-card failure in REY, row B
Ağ — transit ve peering — REY · Bant dışı yönetim — REY
Zaman çizelgesi
-
Çözüldü
Every machine in row B has been reachable since 22:22 UTC. Duration of the outage: 54 minutes. The failed card is being replaced under an existing maintenance window; the replacement does not require another interruption. Affected machines receive the SLA extension automatically.
-
İzleniyor
All 14 affected ports are up on the surviving card. We are checking each machine individually before closing this.
-
Neden belirlendi
A line card in one of the two core switches in REY failed. Row B was dual-homed, but the failover on 14 ports did not complete because the standby links were still training. We are forcing those ports over to the surviving card.
-
İnceleniyor
Machines in row B of REY lost network connectivity at 21:28 UTC. Rows outside B are unaffected. Engineers are on the floor.
Bir olay sonrası inceleme, çözümden itibaren beş gün içinde burada yayımlanır.
Saatler, saat diliminizde () gösterilir.
İlgili sayfalar
- Hizmet durumugpuserver.io'nun her bileşeni ve veri merkezi, beş şehirden 60 saniyede bir yoklanır; 90 günlük kullanılabilirlik ve 2022'den beri olay logu burada yer alır.
- Olay geçmişigpuserver.io'da izlemenin başladığı Eylül 2022'den bu yana yaşanan her olay ve bakım penceresi, ay ay, zaman çizelgesi ve olay sonrası incelemesiyle birlikte.
- Hizmet seviyesi sözleşmesi%99,9 taahhüdü: neyin kesinti sayıldığı, dışarıdan nasıl ölçüldüğü, kaybedilen her dakika için beş dakika süre iadesi ve istisnaların tamamı.
- Ağ25 Gbit/s'e kadar sayaçsız portlar, site başına iki operatör ve bir IX, sürekli DDoS filtreleme, yönlendirilen IPv6 — ve baştan belirtilen, sunmadığımız dört şey.