Alle 6 Rechenzentren betriebsbereit

Bezahlung in Krypto · Keine Identitätsprüfung · Root-Zugriff in unter 5 Minuten

Erheblich Behoben

Core switch line-card failure in REY, row B

Netzwerk — Transit & Peering — REY · Out-of-Band-Management — REY

Zeitleiste

  1. Behoben

    Every machine in row B has been reachable since 22:22 UTC. Duration of the outage: 54 minutes. The failed card is being replaced under an existing maintenance window; the replacement does not require another interruption. Affected machines receive the SLA extension automatically.

  2. Beobachtung

    All 14 affected ports are up on the surviving card. We are checking each machine individually before closing this.

  3. Ursache erkannt

    A line card in one of the two core switches in REY failed. Row B was dual-homed, but the failover on 14 ports did not complete because the standby links were still training. We are forcing those ports over to the surviving card.

  4. Untersuchung läuft

    Machines in row B of REY lost network connectivity at 21:28 UTC. Rows outside B are unaffected. Engineers are on the floor.

Eine Nachbesprechung des Vorfalls wird hier innerhalb von fünf Tagen nach der Behebung veröffentlicht.

Anmelden

Konsole, Rechnungen und Out-of-Band-Zugriff.

Noch kein Konto?

Es gibt keine separate Registrierung. Ihr Konto wird bei Ihrer ersten Bestellung angelegt — Sie wählen E-Mail und Passwort im Zahlungsschritt, und die Konsole ist offen, sobald die Maschine es ist.