轻微 已解决

BMC sensor read errors on H100 PCIe nodes in YUL

带外管理——YUL

时间线

  1. 已解决

    Sensor data is complete for every node. Duration: 44 minutes. The fixed firmware is being rolled out during regular maintenance; no host reboot is required.

  2. 观察中

    All 6 BMCs have been reset and report cleanly. Watching for recurrence.

  3. 已确定原因

    A BMC firmware version on 6 nodes has a bug in its sensor polling that surfaces after a long uptime. Resetting the BMC clears it without touching the host; we are doing that node by node.

  4. 调查中

    The BMCs on some H100 PCIe nodes in YUL are returning sensor read errors since 09:58 UTC. Power and temperature readings in the customer area are missing for those machines. The machines themselves are unaffected.