Todos os 6 centros de dados operacionais

Pago em cripto · Sem verificação de identidade · Acesso root em em menos de 5 minutos

Menor Resolvido

BMC sensor read errors on H100 PCIe nodes in YUL

Gerenciamento fora de banda — YUL

Linha do tempo

  1. Resolvido

    Sensor data is complete for every node. Duration: 44 minutes. The fixed firmware is being rolled out during regular maintenance; no host reboot is required.

  2. Em observação

    All 6 BMCs have been reset and report cleanly. Watching for recurrence.

  3. Causa identificada

    A BMC firmware version on 6 nodes has a bug in its sensor polling that surfaces after a long uptime. Resetting the BMC clears it without touching the host; we are doing that node by node.

  4. Investigando

    The BMCs on some H100 PCIe nodes in YUL are returning sensor read errors since 09:58 UTC. Power and temperature readings in the customer area are missing for those machines. The machines themselves are unaffected.

Entrar

Console, faturas e acesso fora de banda.

Ainda não tem uma conta?

Não existe cadastro separado. Sua conta é criada enquanto você faz seu primeiro pedido — você escolhe o e-mail e a senha na etapa de pagamento, e o console já está aberto quando a máquina estiver pronta.