BMC sensor read errors on H100 PCIe nodes in YUL

Bant dışı yönetim — YUL

Zaman çizelgesi

  1. Çözüldü

    Sensor data is complete for every node. Duration: 44 minutes. The fixed firmware is being rolled out during regular maintenance; no host reboot is required.

  2. İzleniyor

    All 6 BMCs have been reset and report cleanly. Watching for recurrence.

  3. Neden belirlendi

    A BMC firmware version on 6 nodes has a bug in its sensor polling that surfaces after a long uptime. Resetting the BMC clears it without touching the host; we are doing that node by node.

  4. İnceleniyor

    The BMCs on some H100 PCIe nodes in YUL are returning sensor read errors since 09:58 UTC. Power and temperature readings in the customer area are missing for those machines. The machines themselves are unaffected.