BMC sensor read errors on H100 PCIe nodes in YUL
Gestión fuera de banda — YUL
Cronología
-
Resuelto
Sensor data is complete for every node. Duration: 44 minutes. The fixed firmware is being rolled out during regular maintenance; no host reboot is required.
-
En observación
All 6 BMCs have been reset and report cleanly. Watching for recurrence.
-
Causa identificada
A BMC firmware version on 6 nodes has a bug in its sensor polling that surfaces after a long uptime. Resetting the BMC clears it without touching the host; we are doing that node by node.
-
Investigando
The BMCs on some H100 PCIe nodes in YUL are returning sensor read errors since 09:58 UTC. Power and temperature readings in the customer area are missing for those machines. The machines themselves are unaffected.