Degraded optic on the NL-ix port in AMS
Rete — transito e peering — AMS
Cronologia
-
Risolto
All NL-ix sessions in AMS are up with zero errors for 17 minutes. Duration: 1 h 20 min. Latency to exchange peers was a few milliseconds higher during the detour.
-
In osservazione
The optic has been replaced and the port is back up with clean counters. Peering sessions are re-establishing.
-
Causa individuata
The receive power on the optic has dropped below threshold. We have shut the port; traffic to exchange peers is going via Lumen and Cogent while an engineer replaces the optic.
-
In analisi
The NL-ix port in AMS is showing a rising CRC error count since 08:48 UTC. A small share of traffic over the exchange is being retransmitted. Transit paths are unaffected.