轻微 已解决

Elevated inlet temperature in STO, row A

电力与散热——STO

时间线

  1. 已解决

    Row A is back at target. Duration: 22 minutes. No machine throttled and nothing was interrupted.

  2. 已确定原因

    A blanking panel was removed during a machine swap and not replaced, letting hot exhaust recirculate to the neighbouring rack. It has been put back.

  3. 调查中

    Inlet temperatures in row A of STO are 4–6 °C above target since 11:01 UTC. No GPU has throttled yet. We are looking for the cause with the facility.