Elevated inlet temperature in STO, row A
电力与散热——STO
时间线
-
已解决
Row A is back at target. Duration: 22 minutes. No machine throttled and nothing was interrupted.
-
已确定原因
A blanking panel was removed during a machine swap and not replaced, letting hot exhaust recirculate to the neighbouring rack. It has been put back.
-
调查中
Inlet temperatures in row A of STO are 4–6 °C above target since 11:01 UTC. No GPU has throttled yet. We are looking for the cause with the facility.