All 6 data centres operational

Paid in crypto · No identity check · Root access in under 5 minutes

Minor Resolved

Elevated inlet temperature in STO, row A

Power & cooling — STO

Timeline

  1. Resolved

    Row A is back at target. Duration: 22 minutes. No machine throttled and nothing was interrupted.

  2. Identified

    A blanking panel was removed during a machine swap and not replaced, letting hot exhaust recirculate to the neighbouring rack. It has been put back.

  3. Investigating

    Inlet temperatures in row A of STO are 4–6 °C above target since 11:01 UTC. No GPU has throttled yet. We are looking for the cause with the facility.

Sign in

Console, invoices and out-of-band access.

No account yet?

There is no separate sign-up. Your account is created while you place your first order — you choose the email and the password on the payment step, and the console is open by the time the machine is.

Configure a server

Language