Todos los 6 centros de datos operativos

Pagado en cripto · Sin verificación de identidad · Acceso root en en menos de 5 minutos

Mayor Resuelto

Core switch line-card failure in ZRH, row C

Red — tránsito y peering — ZRH · Gestión fuera de banda — ZRH

Cronología

  1. Resuelto

    Every machine in row C has been reachable since 07:12 UTC. Duration of the outage: 50 minutes. The failed card is being replaced under an existing maintenance window; the replacement does not require another interruption. Affected machines receive the SLA extension automatically.

  2. En observación

    All 13 affected ports are up on the surviving card. We are checking each machine individually before closing this.

  3. Causa identificada

    A line card in one of the two core switches in ZRH failed. Row C was dual-homed, but the failover on 13 ports did not complete because the standby links were still training. We are forcing those ports over to the surviving card.

  4. Investigando

    Machines in row C of ZRH lost network connectivity at 06:22 UTC. Rows outside C are unaffected. Engineers are on the floor.

Una revisión posterior al incidente se publica aquí en un plazo de cinco días tras la resolución.