PDU fault in rack AMS-B06

Güç ve soğutma — AMS · Bant dışı yönetim — AMS

Zaman çizelgesi

  1. Çözüldü

    Every machine in rack B06 has been up since 02:52 UTC. Duration: 16 minutes. The PDU is being replaced; the 8 machines that lost power receive the SLA extension automatically. Data on local disks is intact; the machines simply rebooted.

  2. Neden belirlendi

    The A-side PDU in rack B06 failed with a breaker fault. The 8 machines that rebooted are the ones whose B-side supply was not seated correctly after a recent hardware change. All are powered from the B-side now and are booting.

  3. İnceleniyor

    8 machines in rack B06 of AMS lost power at 02:36 UTC. Machines in the rack are dual-fed, but these 8 rebooted when one PDU failed. Engineers are at the rack.

Olay sonrası inceleme ·

Ne oldu ve ne değişti

Neden

The A-side PDU in AMS-B06 suffered a breaker fault. Every machine in the rack has two power supplies on separate feeds, but on 8 of them the B-side cord had been left partially seated during a hardware change the previous week, so they lost power when the A side went.

Etki

8 machines rebooted and were unavailable for 16 minutes. No data was lost; the machines came back to the state they were installed in, with local disks intact.

Neyi değiştirdik

  • Every hardware change now ends with a power-redundancy test: each feed is dropped in turn and the machine must stay up.
  • The faulty PDU model is being phased out across the fleet.
  • Term extensions were applied to the 8 machines the same day.