PDU fault in rack AMS-B06
Strom & Kühlung — AMS · Out-of-Band-Management — AMS
Zeitleiste
-
Behoben
Every machine in rack B06 has been up since 02:52 UTC. Duration: 16 minutes. The PDU is being replaced; the 8 machines that lost power receive the SLA extension automatically. Data on local disks is intact; the machines simply rebooted.
-
Ursache erkannt
The A-side PDU in rack B06 failed with a breaker fault. The 8 machines that rebooted are the ones whose B-side supply was not seated correctly after a recent hardware change. All are powered from the B-side now and are booting.
-
Untersuchung läuft
8 machines in rack B06 of AMS lost power at 02:36 UTC. Machines in the rack are dual-fed, but these 8 rebooted when one PDU failed. Engineers are at the rack.
Nachbesprechung des Vorfalls ·
Was passiert ist und was sich geändert hat
Ursache
The A-side PDU in AMS-B06 suffered a breaker fault. Every machine in the rack has two power supplies on separate feeds, but on 8 of them the B-side cord had been left partially seated during a hardware change the previous week, so they lost power when the A side went.
Auswirkung
8 machines rebooted and were unavailable for 16 minutes. No data was lost; the machines came back to the state they were installed in, with local disks intact.
Was wir geändert haben
- Every hardware change now ends with a power-redundancy test: each feed is dropped in turn and the machine must stay up.
- The faulty PDU model is being phased out across the fleet.
- Term extensions were applied to the 8 machines the same day.
Zeiten werden in Ihrer Zeitzone angezeigt ().
Verwandte Seiten
- ServicestatusLive-Status jeder gpuserver.io-Komponente und jedes Rechenzentrums, alle 60 Sekunden aus fünf Städten gemessen, mit 90-Tage-Verfügbarkeit und Protokoll seit 2022.
- VorfallshistorieJeder Vorfall und jedes Wartungsfenster auf gpuserver.io seit September 2022, mit Zeitleiste und Nachbesprechung des Vorfalls.
- Vereinbarung zum ServicelevelDie 99,9-%-Zusage: was als Ausfallzeit zählt, wie sie von außen gemessen wird, fünf Minuten Laufzeit zurück je verlorener Minute, und die Ausschlüsse vollständig.
- NetzwerkPorts ohne Volumenbegrenzung bis 25 Gbit/s, zwei Carrier und ein IX pro Standort, ständige DDoS-Filterung, geroutetes IPv6 — und vier Dinge, die wir nicht anbieten.