Loss of external connectivity in AMS
Ağ — transit ve peering — AMS · Bant dışı yönetim — AMS
Zaman çizelgesi
-
Çözüldü
AMS has been fully reachable since 18:00 UTC. Duration: 10 minutes. Workloads kept running; every machine in the site receives the SLA extension automatically.
-
Neden belirlendi
A configuration push to the two core switches in AMS was applied in the wrong order and removed the external VLAN from both before re-adding it. The push has been rolled back.
-
İnceleniyor
All machines in AMS became unreachable from outside at 17:50 UTC. Both transit carriers and the exchange are down simultaneously, which points at something inside the site rather than at a carrier.
Olay sonrası inceleme ·
Ne oldu ve ne değişti
Neden
A configuration change intended to be applied to one core switch at a time was pushed to both at once by the automation, because the change set was tagged with the site rather than with a single device. The change removed and re-added the external VLAN; with both switches doing it simultaneously there was no path out of the site for 10 minutes.
Etki
Every machine in AMS was unreachable from the internet for 10 minutes. Out-of-band access went down with it because the management network shares the same uplinks. No workload was interrupted and no data was lost.
Neyi değiştirdik
- The automation now refuses to target more than one core device per site in a single change, without exception.
- The out-of-band network in every site now has an independent uplink so that we retain console access during an event of this kind.
- Term extensions were applied to every machine in AMS.
Saatler, saat diliminizde () gösterilir.
İlgili sayfalar
- Hizmet durumugpuserver.io'nun her bileşeni ve veri merkezi, beş şehirden 60 saniyede bir yoklanır; 90 günlük kullanılabilirlik ve 2022'den beri olay logu burada yer alır.
- Olay geçmişigpuserver.io'da izlemenin başladığı Eylül 2022'den bu yana yaşanan her olay ve bakım penceresi, ay ay, zaman çizelgesi ve olay sonrası incelemesiyle birlikte.
- Hizmet seviyesi sözleşmesi%99,9 taahhüdü: neyin kesinti sayıldığı, dışarıdan nasıl ölçüldüğü, kaybedilen her dakika için beş dakika süre iadesi ve istisnaların tamamı.
- Ağ25 Gbit/s'e kadar sayaçsız portlar, site başına iki operatör ve bir IX, sürekli DDoS filtreleme, yönlendirilen IPv6 — ve baştan belirtilen, sunmadığımız dört şey.