All 6 data centres operational

Paid in crypto · No identity check · Root access in under 5 minutes

Critical Resolved Review published

Out-of-band network partition in STO

Out-of-band management — STO

Timeline

  1. Resolved

    Out-of-band access in STO has been stable since 20:33 UTC. Duration: 25 minutes. Any reinstall or power action queued during the window has been retried and completed.

  2. Monitoring

    Consoles are reachable again. We are restoring the state sync between the two firewall members.

  3. Identified

    The firewall pair in front of the STO management network lost its state synchronisation and both members went passive. We have forced one member active.

  4. Investigating

    No IPMI or KVM console in STO is reachable since 20:08 UTC. Production traffic is unaffected. Reinstalls and power actions from the customer area will fail for machines in STO until this is fixed.

Post-incident review ·

What happened, and what changed

Cause

A firmware update on the management-network firewall pair in STO reset the state-synchronisation key on one member. When the heartbeat failed, both members concluded the other was active and went passive.

Impact

IPMI, KVM, reinstalls and remote power actions were unavailable in STO for 25 minutes. Production connectivity, workloads and data were unaffected.

What we changed

  • Firewall firmware updates are now applied one member at a time with an explicit failover test between the two.
  • The split-brain guard was changed so that a member with a healthy upstream link stays active rather than going passive.